Retrotec DucTester 341 Bedienungsanleitung Seite 39

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 83
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 38
Page 39 of 83
©Retrotec Inc. 2014
20. With DucTester fan off, set the Blower Door to 25 Pa by pressing [Set Pressure] [25] [Enter] on
the Blower Door gauge.
Figure 30: Method #2: Duct Leakage to Outdoors, under depressurization
21. Press [@] if required to remove extrapolation; “@ is Off should then be displayed on the DucTester
gauge.
22. Set the DucTester to 0 Pa by pressing [Set Pressure] [0] [Set] on DucTester gauge.
23. When 0 Pa +/ 1 is achieved on the DucTester gauge, record “Flow” from the DucTester gauge, which
is Duct Leakage to Outdoors.
Figure 31: Method #2 Duct Leakage to Outdoors, under pressurization
8.3 Duct Leakage to Outdoors with 1 gauge and 2 fans
Seitenansicht 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 82 83

Kommentare zu diesen Handbüchern

Keine Kommentare